Study of Backup Power System Analysis (Emergency Generator) for Electricity Dision at West Sumatra Shipping Polytechnic

Authors

  • Raden Roro Anggun Tutur Winasis Ekasakti University, Padang, Indonesia
  • Yani Ridal Ekasakti University, Padang, Indonesia
  • Chairul Nazalul Anshar Ekasakti University, Padang, Indonesia

DOI:

https://doi.org/10.38035/dijdbm.v6i5.5200

Keywords:

Backup Power, Emergency Generator, Demand Factor, Generator Utilization

Abstract

This study aims to analyze the performance of the backup power system (emergency generator) at the West Sumatra Maritime Polytechnic. The reliability of the electricity supply is very important to support the continuity of educational activities and institutional operations. A backup power system is needed to anticipate power outages that can hamper these activities. This study was conducted using the method of literature study, field observation, interviews, documentation, and analysis of technical data obtained. That generator 1 received a load of 172.76 kVA (138.21 kW) and generator 2 of 294.62 kVA (235.70 kW), with a larger load distribution on Generator 2. The demand factor was 35.37% (generator 1) and 58.92% (generator 2), respectively, while the load factor was 0.35368 and 0.58924. These values indicate that the actual load has not reached the maximum capacity of the generator, so there is still a power reserve available. The utilization rate of generator 1 is 28.29% and generator 2 is 47.14%, which means both are still operating within safe limits, even though generator 2 is utilized more. During 5 hours of operation, fuel consumption is 225 liters and 255 liters, respectively, proportional to the size of the load carried. Voltage drops are still within the tolerance limit (?5%), namely 2.53 Volts on generator 1 and 2.40 Volts on generator 2. Power losses in the 360 mm² NYFGbY cable are also relatively small, namely 4.164 kW and 3.76 kW, which indicates the efficiency of the electrical system installation. Thus, the existing backup power system is still reliable and efficient, although further evaluation is needed for load distribution and performance optimization.

References

IEC 60034. (2017). Rotating Electrical Machines. International Electrotechnical Commission.

IEEE Std 446-1995. (1995). IEEE Recommended Practice for Emergency and Standby Power Systems for Industrial and Commercial Applications. Institute of Electrical and Electronics Engineers.

Jimmy, M. A. F., Yassir, & Hasanuddin, T. (2022). Studi Sistem Back UP Beban Emergency Generator dengan Start Up Diesel Engine Generator 760 KW di Unit 2 PT. Pupuk Iskandar Muda. PT. Pupuk Iskandar Muda.

Khairullah, T., Taufik, & Radhiah. (2023). Analisa Penggunaan Diesel Generator Set (53-GH 7001) di PT Pupuk Iskandar Muda Menggunakan MATLAB. PT. Pupuk Iskandar Muda.

Muranto, N., Atmam, & Zulfahri. (2018). Studi Peralihan Daya Listrik dari PLN ke Generator Set (Genset) ketika Terjadi Pemadaman dari PLN dengan Uninterruptible Power Supply (UPS) pada Hotel Grand Elite Pekanbaru. Hotel Grand Elite Pekanbaru.

NFPA 110. (2019). Standard for Emergency and Standby Power Systems. National Fire Protection Association.

Peraturan Pemerintah No. 51 Tahun 1995. Tentang Usaha Penunjang Tenaga Listrik.

PUIL 2000. Persyaratan Umum Instalasi Listrik. Departemen Energi dan Sumber Daya Mineral.

SNI 04-6958-2003. (2003). Spesifikasi Umum Mesin Diesel Generator Set. Badan Standardisasi Nasional.

UU No. 18 Tahun 1999. Tentang Jasa Konstruksi.

Downloads

Published

2025-08-09